Home
Documents and Lists
Create
Site Settings
Help
Up to GSI Client Project Portals
PM Routines Library - BETA SITE (In Development)
PM Routines Library
: Door, Fire Doors, Sliding
New Item
|
Edit Item
|
Delete Item
|
Alert Me
|
Go Back to List
Title:
Door, Fire Doors, Sliding
Level 1 Major Group:
B: SHELL
Level 2 Group:
B20 Exterior Enclosure
Level 3 Individual Elements:
B2030 EXTERIOR DOORS
Frequency:
Quarterly
Preventative Maintenance:
1. Clean track.
2. Lubricate pulleys.
3. Inspect cable or chain for wear or damage and proper threading through pulleys.
4. Replace fusible links or other heat activated devices that have been painted. Check operation of other heat activated devices.
5. Permanently remove obstructions that prohibit movement of door.
6. Check operation of door by disconnecting or lifting counterweight or other appropriate means.
7. Check fit of door in binders and fit against stay roll.
8. Check door for breaks in covering and examine for dry rot.
9. Fill out maintenance checklist and report deficiencies.
Safety Warnings or Special Precautions:
Tools & Materials Required:
Attachments:
Created at 5/29/2008 1:55 PM by
Anna Carey
Last modified at 5/29/2008 1:55 PM by
Anna Carey